Across European industry, many plants still run a SCADA installed years ago. It works, it drives the machines, it shows the mimics in the control room. The limit appears when the data is needed outside that room: several sites to compare, a history to analyze, maintenance to plan remotely. Replacing the SCADA means a shutdown, a rewrite and a recommissioning – a risk few plant managers will take on a line that is producing. SCADA modernization has a lower-risk path: flank the existing system instead of ripping it out.
You do not have to switch the SCADA off to get industrial IoT monitoring: an edge gateway reads the same devices in parallel, keeps the data locally when the network drops and sends it over an outbound connection on port 443. Control stays where it is; only the destination of the data changes.
What stays where it is
PLCs, control logic, interlocks and safety functions, machine HMIs: all of them stay local, as they should. Process control must never depend on an internet link, and no monitoring project should ask to touch it. The edge gateway observes the plant; it does not command it. The SCADA keeps running the control room, and the people who use it every day change nothing.
What moves to the edge gateway
The gateway is a small computer installed in the cabinet or on the plant network. The gateway of NeMo, our industrial telemetry platform, does four things.
It reads devices over Modbus TCP
Energy meters, inverters, PLCs and field instruments almost always speak Modbus, and the gateway polls them as a Modbus TCP client, register by register, at the interval configured for each. Many field devices answer only one request at a time on a connection, so the gateway keeps one transaction in flight per connection: it reads devices that share a connection in series and devices on different connections in parallel. A device that stops answering does not slow down the others.
It does not lose data when the network drops
When the link goes down, the gateway keeps acquiring and stores readings in a local buffer, which by default holds up to 4 GB and 168 hours of data. When the link returns, live readings go out first and the backlog follows, oldest first, with its original timestamps: dashboards are current again at once while the history fills in behind them. If the buffer fills up, it thins the oldest history instead of stopping: a running gateway always records what the plant is doing.
It talks to the cloud outbound only
Towards the cloud the gateway uses MQTT over encrypted WebSocket and HTTPS, on port 443 and outbound only: no inbound port is opened on the plant network from the internet. For the IT and OT security team this is a substantive difference: no plant service is exposed to the internet.
It has its own identity
Each gateway generates its own ECDSA P-256 key pair and receives a certificate when it is activated, and the activation has to be approved on the cloud side before the gateway goes into service: an unregistered box never joins the fleet. The device is designed to sign its activation request with a key held in its TPM.
The SCADA can keep reading
Sometimes the reverse path is needed too: a PLC or the SCADA itself must read a value the gateway already collects, without a second connection to the device. The NeMo gateway can therefore also act as a Modbus TCP server towards the plant. The function is in beta and off by default; once enabled, the gateway exposes the values on a configured register map and keeps them current even when the cloud link is down.
Writes: coming, and controlled
In production the NeMo gateway only reads, which is the right default for a monitoring system. Writes from the cloud are in development and follow the same principle: a request targets a single register, and is accepted only if the device configuration declares it writable, within minimum and maximum limits and, by default, with an explicit confirmation. The request names a register, never an address or a function code: the gateway derives everything else from the applied configuration and keeps a ledger of every write it performs.
Devices that do not speak Modbus TCP
In production the NeMo gateway acquires over Modbus TCP, the common denominator of meters, inverters and PLCs; serial Modbus RTU equipment connects through a serial-to-Ethernet converter. CAN bus reading is already integrated and in beta, while OPC UA, the OPC Foundation architecture released in 2008, and SNMP, the management protocol of network equipment, are on the roadmap. If a plant has equipment that speaks only OPC UA or SNMP, that is the first point to check in the device survey.
What reaches the cloud
Data arrives in real time on the NeMo platform, presented on the Nexilica systems page and on nemo.nexilica.com: ready-made Grafana dashboards, a REST API documented in OpenAPI to feed other systems, role-based access and per-customer data segregation. Several sites, each with its own gateway, end up in one place, including sites in different countries. When the energy meters are among the devices read, the same history supplies the measured consumption, not estimates from bills, that a mandatory energy audit rests on.
What we learned in the field
Modbus as the manuals describe it and Modbus as the cabinets speak it are not the same thing. The most useful surprises apply to any plant:
- A PLC answers even where there is nothing. It can return a plausible value for any address, including addresses of variables that do not exist: a mistake in the register map does not raise an exception, it returns a number. That is why comparing with the SCADA, step 3 below, is not optional.
- Word order is decided register by register. On the same port, the same device can use big-endian for its 64-bit values and swapped words for its 32-bit ones. Decoded the wrong way, a meter reading grows by four orders of magnitude.
- Some meters accept a single TCP session. If the SCADA already holds it, the gateway cannot get in: check it during the survey, before installation.
- A closed socket is not a dead bus. Some devices close the connection after every exchange, and at first sight they look faulty.
- A missing device can be the normal state. Equipment that is switched off or in standby can answer that it is not present: retrying the read costs minutes per device and stretches the cycle for all the others. That answer has to be logged, not retried.
- The supervision export is not the plant. Its variable list can declare equipment that is not installed and leave out blocks that are. The survey has to be checked in the field.
- A dead half must not stall the live half. With serial polling, every unreachable device costs a connect timeout and slows down the reachable ones too: that is why the NeMo gateway polls every connection concurrently with the others.
- After an outage, the present comes first. After a long outage, if live data queues behind the backlog, dashboards lag until the backlog drains: that is why the NeMo gateway sends live readings first.
- Open the firewall by port or hostname. The cloud's IP address can change, port 443 does not: a rule written on the IP will block the gateway sooner or later.
Where to start
- Survey the devices. Which equipment, over which protocol, which registers are needed and how often, and which devices accept only one connection. The SCADA already holds most of this information, and it is where the gateway configuration starts.
- Start with a pilot site. One gateway next to the SCADA, on the same devices, without touching control.
- Compare for a few weeks the gateway data with the SCADA data: this is where phantom variables and swapped words surface, and it proves the readings are right before reports and alarms are built on top.
- Decide what moves. Cross-site comparison, history, cloud alarms: the SCADA remains the tool to run the plant, the platform becomes the tool to analyze it.
Modernizing plant monitoring does not mean rebuilding the plant: it means getting the data out without touching control. If you have a SCADA to flank or several sites to compare, see how we approach software development for industry or get in touch: we start from a survey of your devices.